Dzelzavas street 120g, Riga, LV-1021
+371 67506650
birojs@lafipa.lv

Ouman

WL-TEMP-RH-VOC

245,48 

Price with VAT:

Description

Wireless room temperature, humidity and VOC sensor:
• Sensor can be used with 5 VDC power supply and it can be a repeater.
• Selectable TVOC or CO2eq measurement (Selection is base station specific for all sensors of this type)
• Room sensor has temperature and humidity measurement and also ”AUX-screw connector”
• NTC10, ON/OFF state, transmitter or water leak sensor 0..100% can be connected to AUX- screw connector.
• Battery charge descent doesn’t decrease signal strength.
• Operating frequency 869MHz (6LoWPAN technology)
Technical information:
• Case: ABS plastic
• Dimensions: 90 x 96 x 26 mm
• Installation: Surface installation
• Operating voltage: 5 VDC
• Operating temperature: -40…+85 °C
• Protection class: IP20
• Temperature:
• Meas. accuracy +10...60°C: ± 0,3°C
• Measurement area: -30...+100°C
• Humidity:
• Meas. accuracy 20...80%rH: ± 3 %rH
• Measurement area: 0...100%rH
• VOC / CO2eq:
• Measurement unit: Selectable TVOC or CO2eq measurement. (Selection is base station specific for all sensors of this type)
• Meas. accuracy TVOC & CO2 eq: 15 % of measurement value
• Measurement area TVOC: 0 ... 60 000 ppb (parts per billion)
• Measurement area CO2eq: 400 ... 60 000 ppm (parts per million)
• Stabilation time: 60 h
• Any of the following measurements can be implemented by using the AUX connection:
• AUX temperature measurem:
• Measurement accuracy (25 °C): ± 0.3°C
• Measurement area: -30°C...+50°C
• AUX 0-10VDC transmitter:
• Measurement area: scaleable
• Measurement accuracy: 0.5% / 50mV

Technical specification

ArticleWL-TEMP-RH-VOC 2.1
ProducerOuman
Type of sensor Temperatūra/Relatīvais mitrums
Ask a question

Raivis Kolovza

Automation and monitoring system specialist